Production information
net-line FW-5-Gate | Micro Telecontrol Station
2 Ethernet LAN TCP / IP connections | |
2 RS-485 field interfaces | |
CL/S0 meter interface in FW-5-GATE-cl | |
RS-232/V.24 interface | |
Temperature sensor, -20° to 100° C | |
Integrated wide range power supply unit, 20 to 72 V DC | |
or 230 V AC power supply in FW-5-GATE-230 | |
FW-5-Gate - Compact and smart!
More communication possibilities even in smaller spaces, integrated inputs/outputs have been omitted. The FW-5-GATE can also be supplemented with expansion modules and interface modules. Cost-effective solutions for intelligent secondary distribution networks and smart metering through further interfaces with SML/SyM² meter integration, among others. An integrated temperature sensor measures the station temperature, which can be used e.g. for overload checks on a transformer.
- Deployment as Transparent Protocol Converter
From setIT V5.3.7 respectively V5.4. (for CL versions ) the FW-5-GATE can also be operated in the "Protocol converter" mode. In this case, the device enables the conversion of the following protocols, without that any process data needs to be configured:
- IEC -101 to IEC -104
- IEC -101 to IEC -104 (VPN encrypted)
- IEC -104 to IEC -104 (VPN encrypted)
- IEC -104 to IEC -101
The connection can be established parallel to several control centers.
- Fields of use
- Intelligent secondary unit substation with integration of earth fault/short circuit indicators, network analysis systems and protective devices
- Smart meter integration in energy management systems and remote meter reading control centers
- Intelligent measurement point for wide range of regulation in distribution networks
- Field devise in transformer substations with protection device coupling
- Monitoring of media and infrastructure systems in pipelines
Specifications
- Technical data: net-line FW-5-Gate
Construction | Substation/bay control, telecontrol and automation system in plastic housing, expandable with I/O and communication modules for DIN rail mounting |
Communication | 2 Ethernet LAN TCP/IP, 10/100BaseTx, auto-MDIX, auto-negotiation 1 EIA/RS-485 interface, galvanically isolated 1 EIA/RS-485 meter interface or CS/S0 interface, galvanically isolated 1 EIA/RS-232/V.24 interface |
Inputs/outputs | Sensor for ambient/transformer temperature, -20° to 100° C ±2° C,up to 12 expansion modules for operation of single-/double-point, transformer tap and alarm signals, measurands, metered values, single, double and transformer tap commands, set points, metered value pulse outputs |
Input/output | single-point, double-point, transformer tap position and alarm signals, measurands, metered values, single, double and transformer tap commands, set points, metered value pulse outputs , expandable up to 12 I/O modules |
Protocols | IEC 61850 · IED and protective equipment IEC 60870-5-101 · telecontrol technology, station control technology IEC 60870-5-103 · protective equipment IEC 60870-5-104 · TCP/IP link to control centre IEC 62056-21 · smart meter link (former IEC 1107) SML · SyM² smart meter link via Ethernet DNP3 · server serial/IP DSfG · natural gas interface Modbus RTU/TCP · master/slave Profibus-DP slave, MPI/3964R/RK512 · field bus SNMP · network management NTP/SNTP/DCF · clock synchronisation VPN-Tunnel · IPsec IKEv1/IKEv2, OpenVPN |
PLC programming | IEC 61131-3 compatible via codeIT, 128 kb program memory |
CPU-5E series5e | RISC processor Cortex-A8, 1200 MIPS@800MHz, FPU, watchdog, real-time clock 1GB memory (512 MB SDRAM, 512 MB SLC Flash) |
Memory expansion | optional SD card up to 8 GB, 1 GB up to setIT V5 |
Real-time clock | Errors max. ±20 ppm over entire temperature range, maintenance-free buffer, daylight saving time changeover, leap year correction |
Status displays | LED in front panel for system, communication and binary process values detailed diagnostics via integrated web server |
Operational controls | PLC switch in front panel RUN/RUN-P/STOP USB pushbutton for configuration/backup/recovery functions |
Programming interface | Ethernet LAN 10/100BaseTx, auto-MDIX, USB 2.0 device 12 Mbit/s, USB 2.0 host 12 Mbit/s (configuration/archive synchronisation via stick) |
Fault signal output | to be configured to relay output, parameterisable sys-LED |
Power supply | +20 to 72 V DC max. 5 W, (24 V DC 0.2 A/60 V DC 0.1 A) without expansion Power failure management with power failure buffering 24 V DCvia expansion module PS-60 |
Dielectric strength | 5 kV surge supply & process I/O to PE, according to class VW3 2.5 kV surge, supply to measurands, EIA/RS-232, USB |
Standards | EMC: IEC 60870-2-1, EN 61000-4-x, EN 55022, Insulation: IEC 60870-2-1, IEC 60255-5 NSRL: DIN EN 60950 |
Housing | Micro, polyamide V0, IP20, weight: 240 g, FW-5-GATE-230 300 g dimensions W×H×D: 45×105×115 mm; FW-5-GATE-230 68×105×115 mm expansion: 22.5×105×115 mm |
Installation | DIN rail mounting, DIN-EN 60715 TH35 |
Terminals | MSTB removable screw-type or spring terminal, 0.2 bis 2.5 mm2 |
Ambience | −20° to +70°C, from 24 V DC: +60 °C, in the value range from 48 V DC: +60 °C, from 5 EUs: +60 °C Relative humidity < 95%, without condensation |
Ordering Information
Telecontrol | |
FW-5 | micro telecontrol station (Digital Input, Bluetooth, Relay, Analog) |
FW-5-Gate | micro telecontrol station (Ethernet LAN TCP/IP, RS-485, RS-232) |
FW-5-Gate-4G | RTU with 4G mobile radio modem (Ethernet LAN TCP/IP, RS-485, RS-232) |
FW-50 | scalable RTU (4/7/14 slots, up to 224 digital I/O, 112 Analog I/O) |
Substation Automation | |
BCU-50 | Modular bay station controller (14 slots, up to 224 digital I/O*, 112 analog I/O* 6 LAN segments*) |
Communication | |
Remote I/O | Flexible bus extension, an FW-5 /FW-5-GATE Remote extension modules (EWB) of the FW-5 series |
PM-1 | Power measurement terminal for telecontrol and substation automation in micro-housing, polyamide V0, IP20, DIN top-hat rail installation |